Our Datacentre
All our hosted services are hosted in datacentres of the highest quality (Tier5) ensuring physical security, a perfect server environment and continuous Internet access.

Power:

Generators

  • 3 (5 ultimate) x 3.8MVA 11kV diesel driven emergency power
  • Automatic start in less than 1 minute to feed 100% of the facility
  • Once generators are activated there is a 24 x 7 agreement in place with local suppliers to refuel
  • Monthly test of each generator at 100% on permanent load-bank
  • UPS

    Each system comprises a group of 625kVA Hybrid Rotary UPS modules with:
  • N+1 redundancy
  • Able to supply 100% of facility for up to 8hrs
  • Environment:

    Environmental conditions

  • Temperature regulated overall to 21°C+/- 2°C
  • Humidity regulated overall to 50%RH +/- 10%
  • Cooling Systems

  • Two plants each of 3 x 900kWr air-cooled package chillers giving 3600kWr total with N+1 redundancy.
  • Under-floor cooling air distribution filtered to EU4 standard
  • Fire Strategy

  • Use of non-inflammable and low smoke zero halogen materials where possible
  • Very Intelligent Early Warning (V.I.E.W.) detection – above and below raised floor
  • Smoke extract system activated by fire alarm
  • Security

  • Security personnel 24 x 7
  • Full electronic access control system, based on proximity cards with photo and PIN keypads
  • Biometric Palm-scanners in addition for Colocation areas
  • Locks on colocation suites and cabinets
  • Intruder detection system on escape and riser doors
  • CCTV monitoring with recording of all access points and circulation areas
  • Monitoring

  • Local Operations and Control Centre
  • Network Operations Centre (NOC) in Denver, Colorado (Provides disaster recovery backup)
  • 24x7 local monitoring and logging of temperature and humidity conditions and alarms
  • Full perimeter under-floor leak detection linked to building monitoring system
  •